Starting Induction Motor

Starting Induction Motor:

At the time of Starting Induction Motor slip being unity, the load resistance with reference to the approximate circuit model of Fig. 9.23 isStarting in Induction Motormeaning thereby that short-circuit conditions prevail. Therefore, the motor current at starting can be as large as five to six times the full-load current. In comparison the exciting current in the shunt branch of the circuit model can be neglected reducing the circuit to that of Fig. 9.31.

Starting Induction MotorAssuming for simplicity that as a rough approximation

Starting in Induction Motori.e., the magnetizing current is neglected even under full-load conditions. Then

Starting in Induction Motorwhere sfl= full-load slip (2.8%)

The starting torque expressed as ratio of the full-load torque is

Starting in Induction MotorSquirrel-Cage Motors

Direct starting When a squirrel-cage motor is started ‘direct-on-line,’

Starting in Induction Motori.e. starting current equals the short-circuit (blocked-rotor) current.

Starting in Induction MotorThen from Eq. (9.60)

Starting in Induction MotorThis means that when the starting current is as large as five times the full-load current,

the Starting Induction Motor torque just equals the full-load torque. With such a large starting current, the motor must accelerate and reach normal speed quickly otherwise overheating may damage the motor. The load on the motor at the time of starting must, therefore, be very light or preferably the motor must be on no-load.

To protect their supply systems, the electrical utilities have regulations against short-time current peaks; the consumer is heavily penalized through suitable tarrif for such peaks. Therefore, it is only small-size motors that can be started direct on­line. A bulk consumer can start motors up to 10 kW direct-on-line as long as he arranges to stagger the starting of such motors.

Reduced voltage starting The starting current can be reduced to a tolerable level by reduced-voltage starting. This causes the starting torque to reduce heavily as it is proportional to the square of voltage. Such starting can only be carried out on no or light-load. Various methods of reduced voltage starting are discussed below.

Stator-impedance starting Inclusion of resistors or inductors in the three lines feeding the stator of the Starting Induction Motor reduces the stator terminal voltage to x V of the rated voltage V. The initial starting current is then

Starting in Induction MotorSubstituting in Eq. (9.60)Starting in Induction MotorThus, while the starting current reduces by a fraction x of the rated-voltage starting current (4c), the starting torque is reduced by a fraction x2 of that obtainable with direct switching. This method can be used for small motors such as those driving centrifugal pumps; but star-delta starting (given later) is cheaper with better starting torque.

Autotransformer starting Reduced voltage for starting can be obtained from three autotransformers connected in star as shown in the schematic diagram of Fig. 9.32. If the voltage is reduced to a fraction x of the rated voltage V, the motor starting current (initial) isStarting in Induction Motorwhere Isc = starting current (line) with full-voltage The current drawn from the supply is

Starting in Induction MotorStarting Induction MotorThe starting/full-load torque ratio is

Starting in Induction MotorIt is found that while the starting torque is reduced to a fraction x2 of that obtainable by direct starting, the starting line current is also reduced by the same fraction. Compared to stator-impedance starting, the line current reduces further by a fraction x while torque remains the same. The autotransformer starting is much superior to the stator-impedance starting. Further, smooth starting and high acceleration are possible by gradually raising the voltage to the full line value.

After starting, the autotransformer is cut as shown in the wiring diagram of Fig. 9.33. It is to be observed that the autotransformer can be short-time rated. The use of an autotransformer is an expensive way of Starting Induction Motor and is warranted for large motors only.Starting Induction MotorStar-delta starting The star-delta starting is an inexpensive two-step method of Starting Induction Motor. The motor designed for delta running is started across full-line voltage by connecting the phases in star as shown in the schematic diagram of Fig. 9.34.Starting Induction MotorIn direct delta starting:

Starting in Induction MotorIn star starting:

Starting line (phase) current, IS (star)

Starting in Induction Motor

Using Eq. (9.60)Starting in Induction MotorIt is thus seen that star-delta starting reduces the starting torque to one-third that obtainable by direct-delta starting and also the starting line current to one-third. It just acts like autotransformer starting with

Starting in Induction MotorA star-delta starter is much cheaper than an autotransformer starter and is commonly employed for both small and medium-size motors. The wiring diagram of star-delta starting is shown in Fig. 9.35.

Starting of Slip-ring Motors (Rotor-resistance Starting)

It has already been discussed that in slip-ring motors the starting current is reduced and the starting torque simultaneously increased by adding an external resistance in the rotor circuit. Figure 9.35 shows the motor circuit (magnetizing branch neglected) with external resistance added in the rotor circuit. For simplicity, the stator impedance is also neglected. Here

Starting Induction MotorStarting in Induction Motorwhere Rext = actual external resistance in the rotor circuit

NowStarting in Induction MotorMaximum starting torque is achieved at

Starting in Induction Motorwhich equals the breakdown torque or

Starting in Induction MotorBy a suitable choice of Rext the starting current and torque can be both adjusted to desirable levels. Since the maximum starting torque achievable is much more than the full-load torque, the use of slip-ring motors with rotor-resistance starting is ideal for starting on load. The external rotor resistance is arranged in steps which are gradually cut out during starting.

 