No Load Transformer Phasor Diagram

No Load Transformer Phasor Diagram

Figure 3.5 shows the schematic diagram of a two-winding transformer on No Load Transformer Phasor Diagram,

No Load Transformer Phasor Diagram

i.e. the secondary terminals are open while the primary is connected to a source of constant sinusoidal voltage of frequency f Hz. The simplifying assumption that the resistances of the windings are negligible, will be made.

The primary winding draws a small amount of alternating current of instantaneous value i0, called the exciting current, from the voltage source with positive direction as indicated on the diagram. The exciting current establishes flux Φ in the core (positive direction marked on diagram) all of which is assumed confined to the core i.e., there is no leakage of flux. Consequently the primary winding has flux linkages,

Transformer on No-Load

As per Lenz’s law, the positive direction of this emf opposes the positive current direction and is shown by + and — polarity marks on the diagram. According to Kirchhoff’s law,

Transformer on No-Load

and thus e1 and therefore Φ must be sinusoidal of frequency fHz, the same as that of the voltage source. Let

Transformer on No-Load

as the winding resistances in a transformer are of extremely small order. It is, therefore, seen from Eq. (3.6) that maximum flux in a transformer is determined by V1/f(voltage/ frequency) ratio at which it is excited.

According to Eq. (3.6) the flux is fully determined by the applied voltage, its frequency and the number of winding turns. This equation is true not only for a transformer but also for any other electromagnetic device operated with sinusoidally varying ac and where the assumption of negligible winding resistance holds.

All the core flux Φ also links the secondary coil (no leakage flux) causing in it an induced emf of

Transformer on No-Load

It is easy to see that e1 and e2 are in phase. This is so indicated by phasor diagram of Fig. 3.6 where E1 and E2 are the corresponding phasors or in terms of the rms values. As the secondary is open-circuited, its terminal voltage is given as

Transformer on No-Load

From Eqs. (3.1) and (3.8) we have the induced emf ratio of the transformer windings

Transformer on No-Load

This indeed is the transformation action of the No Load Transformer Phasor Diagram. Its current transformation which is in inverse ratio of turns will be discussed in Section 3.4.

The value of exciting current i0 has to be such that the required mmf is established so as to create the flux demanded by the applied voltage (Eq. (3.6)). If a linear B-H relationship is assumed (devoid of hysteresis and saturation), the exciting current is only magnetizing in nature and is proportional to the sinusoidal flux and in phase with it. This is represented by the phasor im in Fig. 3.6, lagging the induced emf by 90°. However, the presence of hysteresis and the phenomenon of eddy-currents, though of a different physical nature, both demand the flow of active power into the system and as a consequence the exciting current I0 has another component Ii in phase with Ei. Thus, the exciting current lags the induced emf by an angle θ0 slightly less than 90° as shown in the phasor diagram of Fig. 3.6. Indeed it is the hysteresis which causes the current component Ii leading Im by 90° and eddy-currents add more of this component.

The effect of saturation nonlinearity is to create a family of odd-harmonic components in the exciting current, the predominant being the third harmonic; this may constitute as large as 35-40% of the exciting current. While these effects will be elaborated in Sec. 3.10, it will be assumed here that the current I0 and its magnetizing component Im, and its core-loss component Ii are sinusoidal on equivalent rms basis. In other words, Im is the magnetizing current and is responsible for the production of flux, while Ii is the core-loss current responsible for the active power being drawn from the source to provide the hysteresis and eddy-current loss.

To account for the harmonics, the exciting current I0 is taken as the rms sine wave equivalent of the actual non-sinusoidal current drawn by the No Load Transformer Phasor Diagram. Since the excitation current in a typical transformer is only about 5% of the

full-load current, the net current drawn by the transformer under loaded condition is almost sinusoidal. From the phasor diagram of Fig. 3.6, the core-loss is given by

Transformer on No-Load

In a practical transformer, the magnetizing current (Im) is kept low and the core-loss is restrained to an acceptable value by use of high permeability silicon-steel in laminated form. From the no-load phasor diagram of Fig. 3.6, the parallel circuit model of exciting current as shown in Fig. 3.7 can be easily imagined wherein conductance Gaccounts for core-loss current Ii and inductive susceptance Bm. for magnetizing current Im. Both these currents are drawn at induced emf E1=V1 for resistance-less, no-leakage primary coil; even otherwise E1≈V1

No Load Transformer Phasor Diagram

MORE RELATED ARTICLE

COPYRIGHT © 2014 TO 2019 EEEGUIDE.COM ALL RIGHTS RESERVED | HOME | SITEMAP | CONTACT US | ABOUT US | PRIVACY POLICY | Frontier Theme