Isolated Induction Generator Working Principle

Isolated Induction Generator Working Principle:

An Isolated Induction Generator Working Principle feeding a load is shown in Fig. 9.61. The delta-connected capacitors across the generator terminals provide the magnetizing current necessary to excite the isolated generator. The voltage build-up will be explained later in this section. As the generator is loaded, the operating frequency depends primarily upon rotor speed but is affected by the load, while the voltage is mainly decided by capacitor reactance (Xc) at the operating frequency.

Let

Isolated Induction Generator Working PrincipleIsolated Induction Generator Working PrincipleThe machine slip (which should be negative) can be expressed as

Isolated Induction Generator Working PrincipleAssuming that the machine reactances, excitation reactances and machine induced emf correspond to the rated frequency (ω0), the per phase equivalent circuit of the system at operating frequency ωs = aω0 is drawn in Fig. 9.62 (a) with load considered as purely resistive. Dividing throughout by ‘a’, the circuit is reduced to the rated (fixed) frequency and is drawn in Fig. 9.62 (b).

Isolated Induction Generator Working Principle

Isolated Induction Generator Working Principle

Voltage Build-up                                  Fig. 9.62

With reference to Fig. 9.61, consider that the generator is run at synchronous speed at no-load (switch off) with 4-connected capacitors hanging on its terminals. The rotor circuit behaves as open and so the circuit model is as drawn in Fig. 9.63(a).

Isolated Induction Generator Working PrincipleThe current fed into the motor is I1 = Imag, the magnetizing current. If the voltage drop in stator impedance, R1, X1, is ignored, we have

Isolated Induction Generator Working PrincipleIsolated Induction GeneratorLike in a dc shunt generator, the magnetization characteristic and reactance line are drawn in Fig. 9.63(b). Their intersection gives the no-load voltage. This is the case at rated frequency. V1 will vary slightly as the actual stator frequency changes from the rated value. This variation may be ignored.