Double Circuit Three Phase Lines

Double Circuit Three Phase Lines:

It is common practice to build Double Circuit Three Phase Lines so as to increase transmission reliability at somewhat enhanced cost. From the point of view of power transfer from one end of the line to the other, it is desirable to build the two lines with as low an inductance/phase as possible. In order to achieve this, self GMD (Ds) should be made high and mutual GMD (Dm) should be made low. Therefore, the individual conductors of a phase should be kept as far apart as possible (for high self GMD), while the distance between phases be kept as low as permissible (for loW mutual GMD).

Figure 2.15 shows the three sections of the transposition cycle of two parallel circuit three-phase lines with vertical spacing (it is a very commonly used configuration).

double-circuit-three-phase-lines

It may be noted here that conductors a and a’ in parallel compose phase a and similarly b and b’ compose phase b and c and c’ compose phase c. In order to achieve high Ds the conductors of two phases are placed diametrically opposite to each other and those of the third phase are horizontally opposite to each other. (The reader can try other configurations to verify that these will lead to low Ds.) Applying the method of GMD, the equivalent equilateral spacing is

Double Circuit Three Phase Lines

Where Dab = mutual GMD between phases a and b in section 1 of the transposition cycle

Double Circuit Three Phase Lines

Dbc = mutual GMD between phases b and c in section 1 of the transposition cycle

Double Circuit Three Phase Lines

Dca = mutual GMD between phases c and a in section 1 of the transposition cycle

Double Circuit Three Phase Lines

It may be noted here that Deq remains the same in each section of the transposition cycle, as the conductors of each parallel circuit rotate cyclically, so do Dab, Dbc. and Dca. The reader is advised to verify this for sections 2 and 3 of the transposition cycle in Fig. 2.15.

Self GMD in section 1 of phase a (i.e., conductors a and a’) is

Double Circuit Three Phase Lines

Self GMD of phases b and c in section 1 are respectively

Double Circuit Three Phase Lines

Because of the cyclic rotation of conductors of each parallel circuit over the transposition cycle, DS also remains the same in each transposition section. The reader should verify this for sections 2 and 3 in Fig. 2.15.

The inductance per phase is

Double Circuit Three Phase Lines

The self inductance of each circuit is given by

Double Circuit Three Phase Lines

Equation (2.45) can now be written as

Double Circuit Three Phase Lines

where M is the mutual inductance between the two circuits, i.e.

Double Circuit Three Phase Lines

This is a well known result for the two coupled curcuits connected in parallel (at similar polarity ends).

Double Circuit Three Phase Lines

i.e. the mutual impedance between the circuits becomes zero. Under this condition

Double Circuit Three Phase Lines

The GMD method, though applied above to a particular configuration of a double circuit, is valid for any configuration as long as the circuits are electrically parallel.

While the GMD method is valid for fully transposed lines, it is commonly applied for untransposed lines and is quite accurate for practical purposes.